Frequently Asked Question

For a certain valve, 2 different proof tests with the same valve are required, with a full function test once every 4 years. However the valve is sometimes used during normal operation. This usage during normal operation can be seen as a partial test that
Last Updated 5 years ago

This can be modelled by specifying the full function test as the proof test, and the partial test as the partial valve stroke test. At the bottom of the final element configuration there is a partial valve stroke test checkbox. If this box is checked, the interval and coverage of the partial test can be specified.