Frequently Asked Question
I have defined a wire as a logic solver (without channels). However the PFDavg for the Logic solver is calculated as 0.0E+0 and the SIF PFD average does not calculate.
Last Updated 5 years ago
If you go to the library in your project, then go to logic solver models, and right click view on the wired connection one, there are two things that you need to "fix".
1. The DU failure rate should not be 0.
2. You should select a calculation model (1oo1 for a single wire).
Once you do these two, you will see that the tool calculates.
1. The DU failure rate should not be 0.
2. You should select a calculation model (1oo1 for a single wire).
Once you do these two, you will see that the tool calculates.