Frequently Asked Question

I would like to know which tables from 61511:2016 are considered when using this option for architectural constraints in the SIL verification parameters?
Last Updated 5 years ago

For sensors and final elements, table 6 of IEC 61511-1:2016 is used. For the logic solver the route 1H per IEC 61508-2:2010 is used per clause 11.4.3 in IEC 61511-1:2016.

Please Wait!

Please wait... it will take a second!