Frequently Asked Question

We need to do the SIL Verification of a safety loop which does not include a PLC but goes from the sensor to the final element through direct cabling (TT which stops a motor). How can we do this?
Last Updated 5 years ago

As you may well know, exSILentia "requires" that all three parts of the SIF are configured before the overall SIF is calculated. You therefore need to model a logic solver. in this case you should model this as a "wire", create a user defined logic solver with a lambdaSU of 1e-9 and a lambdaDU of 1e-11, architecture type A. This will yield a result for the logic solver that is significantly low to avoid any impact on your overall SIF.

Please Wait!

Please wait... it will take a second!