Frequently Asked Question
I'm using SILver to verify the SIL level of some existing installations. There's a lot of old instruments so when there's no other option, I have to use the generic data. The PFDavg and architectural constraints are good, but logically the systematic capa
Last Updated 5 years ago
Using non-certified equipment requires justification of the use of that equipment on the basis of prior use. For this reason, we have a proven in use checklist built into the tool. You also have the option to document the proven in use justification elsewhere (outside exSILentia) in you prefer.